What is an auxiliary power supply and how does it work?
Release time:
2026-11-29
Article overview
This guide explains what an auxiliary power supply is, how it converts or conditions power to support critical loads independently from the main supply, and what distinguishes different types in industrial and infrastructure contexts. It covers operating principles, key circuit functions, selection parameters, and relevant EN standards — giving electrical engineers the technical grounding needed to evaluate options during the design or procurement phase.
Table of contents
An auxiliary power supply is a dedicated power source that operates independently from a system's primary supply, providing regulated voltage and current to control circuits, instrumentation, communication modules, or other subsystems that must remain functional even when the main power path is interrupted or unavailable. In industrial automation, rail transport, telecommunications infrastructure, and energy systems, it is not a backup in the casual sense — it is an engineered component with defined input ranges, output tolerances, and protection behaviour that must be specified and selected with the same rigour as any other critical circuit element.
What an auxiliary power supply actually does
The core function is to decouple a subset of loads — typically control logic, sensors, safety relays, or communication interfaces — from the behaviour of the main supply bus. When mains voltage drops, switches between sources, or is intentionally isolated for maintenance, an auxiliary power supply keeps those secondary loads energised and within specification.
This separation matters because control circuits often have different voltage requirements from power circuits. A motor drive, for example, might operate on a 400 V AC three-phase bus, while its internal microcontroller and fieldbus interface need a stable 24 V DC rail at a few hundred milliamps. Deriving that low-voltage rail directly from the mains without isolation and regulation would expose sensitive electronics to transients, voltage sags, and noise that the main bus routinely carries. An auxiliary supply — often called a supplemental power unit or secondary power source in system documentation — solves this by providing galvanic isolation, tight output regulation, and defined hold-up time.
Beyond powering control electronics, auxiliary supplies serve several related roles depending on the application:
- Powering safety and monitoring circuits that must stay active during fault conditions or controlled shutdowns
- Supplying battery charging circuits for integrated battery backup systems, allowing a battery backup system to maintain charge during normal operation and take over seamlessly on loss of mains
- Providing a reference voltage rail for instrumentation amplifiers, signal conditioners, and analogue-to-digital converters that require a stable, low-noise regulated power supply
- Feeding communication and gateway modules — such as industrial Ethernet switches or fieldbus repeaters — that must relay fault data to supervisory systems even when the process is shut down
The distinction between an auxiliary supply and a general power distribution unit or uninterruptible power supply (UPS) is one of scope and architecture. A UPS is typically a system-level solution protecting an entire load — a server rack, a production cell — against outages. An auxiliary power supply is usually a module-level component integrated into a larger device or switchgear cabinet, defined by the specific secondary loads it must support rather than by overall system continuity.
How it works: core operating principles
The internal architecture of an auxiliary power supply depends on whether it is linear or switched-mode, but most modern designs used in industrial environments are switched-mode power supplies (SMPS), sometimes referred to as a DC power converter or power conditioning unit when emphasising signal quality. The operating sequence involves several distinct stages.
Input rectification and filtering
If the input is AC — typically 100–240 V AC for wide-range designs, or a fixed 230 V AC for European installations — the first stage rectifies the alternating waveform to a rough DC bus using a diode bridge, then smooths it with bulk capacitors. This creates an intermediate DC voltage of around 310–340 V DC for a 230 V AC input. Designs intended to accept DC input directly (common in rail transport, where the auxiliary bus may be 24 V DC or 110 V DC) skip the rectifier stage entirely.
High-frequency switching and transformer isolation
The intermediate DC voltage is then switched at high frequency — typically 50 kHz to several hundred kHz — by power transistors (usually MOSFETs or IGBTs). This high-frequency AC is fed through a small ferrite transformer, which provides galvanic isolation between input and output and allows the turns ratio to set the approximate output voltage. The high switching frequency is what makes it possible to use a compact transformer rather than the large, heavy iron-core units needed for 50 Hz operation. This is why modern auxiliary supplies are significantly smaller and lighter than linear equivalents at the same power rating.
Output rectification, filtering, and regulation
The transformer secondary side produces a high-frequency AC signal that is rectified again — typically using Schottky diodes for efficiency — and filtered through inductors and capacitors to produce the final DC output. A feedback loop, usually using an optocoupler to maintain isolation, compares the output voltage to a reference and adjusts the duty cycle of the switching transistors to hold the output within specification regardless of load variations or input fluctuations. This closed-loop regulation is what delivers the tight output tolerance — often ±1% to ±5% depending on grade — expected of a regulated power supply.
Protection functions
Practical auxiliary supplies integrate several protection mechanisms that are essential for safe operation in industrial environments:
- Overvoltage protection (OVP): shuts down or clamps the output if output voltage exceeds a threshold, protecting downstream control electronics from damage
- Overcurrent protection (OCP) / short-circuit protection: limits output current during overload or fault, either by reducing voltage (constant current limiting) or by shutting down and auto-restarting (hiccup mode)
- Overtemperature protection (OTP): reduces output or shuts down if internal temperature exceeds a safe level, relevant in enclosed switchgear cabinets with limited airflow
- Input undervoltage lockout (UVLO): prevents operation below a minimum input voltage where switching behaviour would be unpredictable
Hold-up time and energy storage
A critical parameter that distinguishes a standard regulated supply from one suited for use as a standby power system component is hold-up time: how long the output remains within specification after the input voltage disappears. This is determined primarily by the capacitance on the intermediate DC bus. Typical hold-up times for DIN-rail industrial auxiliary supplies are 20–50 ms at full load, which is usually sufficient to ride through a brief mains interruption or allow controlled shutdown of a process controller. Applications requiring longer ride-through — tens of seconds or minutes — integrate an external battery backup system or supercapacitor bank to extend this window, effectively combining the auxiliary supply with an off-grid power solution architecture.
Types of auxiliary power supply and when each applies
The right architecture depends on input source type, isolation requirements, output voltage, power level, and the operational continuity expected during a mains failure. The table below summarises the main categories used in engineering practice.
| Type | Typical input | Typical output | Key characteristic | Common application |
|---|---|---|---|---|
| AC/DC switched-mode (isolated) | 85–264 V AC | 5 V / 12 V / 24 V DC | Galvanic isolation, wide input range, compact | Industrial automation, PLC control panels |
| DC/DC converter (isolated) | 24 V / 48 V / 110 V DC | 5 V / 12 V / 24 V DC | Isolation between DC buses, voltage conversion | Rail vehicles, battery-backed systems, telecoms |
| DC/DC converter (non-isolated) | 24–48 V DC | 3.3 V / 5 V / 12 V DC | High efficiency, lower cost, no isolation barrier | On-board electronics where common ground is acceptable |
| UPS module / battery-integrated | AC mains + battery | 24 V DC (regulated) | Seamless switchover, extended hold-up | Safety controllers, emergency shutdown systems |
| Linear regulated supply | AC or DC | Low voltage DC | Very low output noise, simple, inefficient | Precision instrumentation, audio, lab equipment |
| Redundant parallel modules | AC mains | 24 V DC (shared bus) | No single point of failure; N+1 architecture | Critical infrastructure, high-availability PLCs |
Onboard auxiliary supplies in rail and vehicle applications
In rail transport, the term auxiliary power unit (APU) or onboard power system refers specifically to the subsystem that derives low-voltage DC from the high-voltage traction bus to power lighting, HVAC control, door systems, and passenger information displays. This is an application where the auxiliary power unit overview provided by IEEE and IEC standards becomes directly relevant — the design must account for a traction bus that varies widely in voltage, is subject to regenerative braking transients, and operates across a broad temperature range. The auxiliary supply in this context is not a commodity component but a custom or semi-custom module qualified to rolling stock standards.
Redundant power modules in industrial automation
For high-availability installations — safety PLCs, process control systems in chemical plants, or server room infrastructure — a redundant power module architecture uses two or more auxiliary supply modules feeding the same output bus through diodes or active ORing circuits. If one module fails, the other carries the full load without interruption. This is conceptually similar to what a backup power unit provides at system level, but implemented at the module level within the cabinet itself. Specifying redundancy requires ensuring that the output voltage of both modules is matched closely enough that one does not carry a disproportionate share of the load current during normal operation.
Key selection parameters for engineers
Selecting an auxiliary power supply for a specific application requires working through a defined set of parameters. Getting these right at the design stage avoids costly retrofits and ensures the supply remains within its safe operating area across all expected conditions.
Input voltage range and source type
The first question is whether the input is AC or DC, and what range it covers. European industrial installations typically use 230 V AC single-phase or 400 V AC three-phase for the main bus, with 24 V DC as the standard control voltage rail in automation — meaning an AC/DC auxiliary supply converting 230 V AC to 24 V DC is the most common configuration in German switchgear cabinets. Wide-range inputs (85–264 V AC) provide flexibility for export products or installations where supply quality is poor. DC input designs are necessary for battery-backed systems, vehicles, and off-grid installations where a battery backup system or accumulator is the primary source.
Output voltage and accuracy
24 V DC dominates industrial automation in accordance with IEC 61131-2 requirements for PLC I/O. Other common output voltages include 5 V DC for legacy logic, 12 V DC for sensors and communication modules, and 48 V DC for telecoms equipment. Output accuracy — the total deviation from nominal under combined load and line variation — should be specified carefully for applications with tight reference voltage requirements. A ±1% accuracy supply is significantly more expensive than a ±5% unit; the difference matters for instrumentation but is usually irrelevant for relay coils.
Output power and current derating
Rated output power must be matched to the total load, with an appropriate margin — typically 70–80% of rated capacity at maximum expected load, to avoid continuous operation at the thermal limit. Equally important is understanding the derating curve: most auxiliary supplies reduce their maximum rated output current at elevated ambient temperatures. A module rated at 10 A at 40 °C may only be rated to 7 A at 60 °C. In enclosed cabinets with high ambient temperatures — common in summer in southern German manufacturing facilities without climate control — ignoring derating is a common cause of premature failure.
Efficiency and thermal management
Efficiency directly affects heat dissipation. A 100 W auxiliary supply operating at 88% efficiency dissipates approximately 13.6 W as heat. In a sealed or poorly ventilated enclosure, this heat must be managed either through natural convection, forced air, or by selecting a supply with higher efficiency. Modern high-quality SMPS designs achieve 90–95% efficiency, which significantly reduces thermal management requirements compared to older or lower-cost alternatives. For applications with many auxiliary supply modules in one cabinet, the aggregate heat load can drive cabinet cooling sizing.
Hold-up time requirements
As noted earlier, hold-up time determines how long the auxiliary supply maintains its output after input loss. Standard 20 ms hold-up is sufficient for most control circuits to complete a safe-state sequence during a brief disturbance. Applications requiring longer continuity — such as systems that must continue logging data for several seconds after mains failure, or that need to execute a controlled shutdown sequence — require either a supply with enhanced hold-up capacitance, an integrated UPS module, or an external energy storage device. For guidance on matching hold-up to application requirements, the backup power supply basics framework published by the U.S. Department of Energy provides useful general principles, though European applications should validate against IEC rather than NEC requirements.
Isolation voltage and leakage current
Galvanic isolation between input and output is a standard feature of most industrial auxiliary supplies. The isolation voltage rating — typically 1.5 kV AC to 4 kV AC test voltage depending on safety class — determines whether the supply meets the creepage and clearance requirements for the target environment. Leakage current is relevant in medical and food processing applications where touch current limits are strictly defined. Standard industrial designs follow IEC 62368-1 (audio/video and IT equipment) or IEC 61558 (transformers and power supplies), depending on the product category.
Protection class and mechanical form factor
DIN-rail mounting (EN 60715 TS35) is the standard form factor for industrial switchgear cabinets in Germany and across the EU. Panel-mount, chassis-mount, and open-frame designs exist for OEM integration. IP protection class — IP20 for cabinet-mounted modules, higher ratings for standalone enclosures — must match the installation environment. Auxiliary supplies for outdoor infrastructure or mobile equipment may require IP54 or higher, which affects both the mechanical design and the thermal management strategy.
EN standards and compliance considerations for the German market
For engineers designing or procuring auxiliary power supplies for the German market, compliance with the relevant European standards is not optional. CE marking is required for products placed on the EU market, and the specific harmonised standards that support the CE declaration determine the technical requirements the supply must meet.
Key harmonised standards
The following standards are directly applicable to most industrial auxiliary power supply products:
- EN 61558-2-16 (switch-mode power supplies): Specifies safety requirements for SMPS with output voltages up to 1,000 V, covering isolation, temperature rise, and dielectric withstand. This is the most commonly cited standard for DIN-rail industrial supplies.
- EN 62368-1: Hazard-based safety standard that has replaced EN 60950-1 (IT equipment) and EN 60065 (audio/video) as of 2021. Many auxiliary supplies for IT and automation environments now require compliance with this standard.
- EN 61000 series (EMC): Emissions and immunity requirements. Auxiliary supplies must meet EN 55032 (or EN 55011 for industrial equipment) for conducted and radiated emissions, and EN 61000-4-x immunity tests including electrostatic discharge (ESD), fast transients (EFT/Burst), and surge. Performance in an EMC-compliant installation also depends on correct cable routing and grounding practice in the cabinet.
- EN 60664-1: Insulation coordination for equipment within low-voltage systems — defines creepage and clearance requirements based on pollution degree, overvoltage category, and rated voltage. This standard underpins isolation voltage specifications.
- EN 50155: Specifically applicable to electronic equipment used in railway rolling stock. If the auxiliary supply is part of a rail vehicle onboard power system, compliance with EN 50155 — covering operating temperatures, vibration, humidity, and input voltage ranges specific to the traction bus — is required.
For a detailed technical reference on how these standards are applied in product certification, the auxiliary power supply standards documentation published by IEEE provides relevant background on design and test methodology.
Overvoltage categories and application context
EN 60664-1 defines four overvoltage categories (OVC I through OVC IV) that classify the expected transient overvoltage at different points in an installation. An auxiliary supply connected directly to the building's incoming supply without an upstream transformer must be rated for OVC III. One installed downstream of an isolation transformer or within a control cabinet — where transients are attenuated by upstream protection — typically needs only OVC II. Misclassifying the installation category leads either to undersized insulation (a safety risk) or unnecessarily expensive overspecification.
Functional safety considerations (IEC 62061 / EN ISO 13849-1)
Where the auxiliary power supply feeds safety-related control circuits — for example, the power supply to a safety relay module or a SIL-rated controller — the supply itself may need to be evaluated as part of the safety function. This does not necessarily mean the supply must carry a SIL rating itself, but its failure modes, diagnostic coverage, and mean time to dangerous failure (MTTFd) must be considered in the overall safety integrity level calculation. Some manufacturers provide SISTEMA-compatible component data sheets that include MTTFd and B10d values for use in EN ISO 13849-1 calculations. If the supply is powering a safety function, verifying the availability of this data before selection avoids redesign at the validation stage.
RoHS and WEEE compliance
All auxiliary power supply modules placed on the German market must comply with the RoHS Directive (2011/65/EU, amended by 2015/863/EU) restricting hazardous substances, and must be registered and managed under the WEEE Directive (2012/19/EU) for electrical and electronic equipment waste. These are not performance specifications but are part of legal market access requirements. For OEM integrators purchasing modules from outside the EU, confirming supplier compliance with these directives before procurement avoids import and customs complications.
Frequently asked questions
What is the difference between an auxiliary power supply and a UPS?
A uninterruptible power supply is a system-level solution designed to protect an entire load — such as a server or control panel — against mains outages, usually by integrating a battery and automatic transfer switching. An auxiliary power supply is typically a module-level component that provides a regulated secondary voltage rail to specific subsystems within a device or cabinet. Many auxiliary supplies include a short hold-up time (20–50 ms) using capacitors, but they are not intended to replace a full UPS where extended continuity is required. In some system architectures, an auxiliary supply and a battery module are combined to create an integrated standby power system that serves both functions.
Can an auxiliary power supply operate from a DC input?
Yes. DC/DC auxiliary supply modules are designed specifically for applications where the available source is a DC bus — such as a 24 V or 48 V control bus, a 110 V DC substation battery, or a vehicle traction supply. These modules use the same switched-mode principle as AC/DC designs but skip the input rectification stage. Isolated DC/DC converters are essential when two DC buses must remain galvanically separated, for example between a battery system and a measurement circuit, or between different voltage domains on the same PCB or in the same enclosure.
What output voltage do most industrial auxiliary supplies use in Germany?
24 V DC is the standard control voltage in German industrial automation, defined in IEC 61131-2 as the nominal voltage for PLC digital I/O interfaces. Almost all DIN-rail auxiliary supply modules sold for switchgear cabinet applications in Germany produce a 24 V DC output from a 230 V AC input. 12 V DC outputs are common for sensors and some communication modules, and 5 V DC outputs are found in legacy systems or for powering microcontroller-based devices. 48 V DC is standard in telecommunications infrastructure.
How do I determine if an auxiliary supply needs redundancy?
Redundancy is justified when failure of the auxiliary supply would result in loss of a safety function, unacceptable production downtime, or loss of data with significant consequences. The decision should follow a formal risk assessment — either as part of an IEC 62061 / EN ISO 13849-1 safety assessment or a business continuity analysis. Practically, any process where the cost of a single unplanned outage exceeds the cost of a second supply module and the associated ORing hardware is a candidate for a redundant power module architecture. The parallel modules must have matched output voltages to ensure proper load sharing, and each module must be individually sized to carry the full load on its own.
What is meant by "low-voltage auxiliary supply" in switchgear documentation?
In switchgear and protection relay documentation, "low-voltage auxiliary supply" refers to the separate DC or AC power source that energises the relay's internal electronics, coils, and communication interfaces, independent of the high-voltage circuit being measured or switched. This is architecturally the same concept as a secondary power source or supplemental power unit: it keeps the control and monitoring functions operational even when the main circuit is de-energised. The rated auxiliary voltage for protection relays in European substations is commonly 48 V DC, 110 V DC, or 220 V DC, depending on the installation's DC battery bus standard.
Previous page
Next page
Dimmable LED driver guide: how to choose the right one for your lighting project
Latest News
DC/DC Converter Power Supply Solution
LED Power Supply Solutions
Medical Power Supply Solutions
LED Display Solutions
Configurable Power Solutions
Building Power Solutions
Product Center
Industrial lithium battery charger
Smart home power supply
LED power supply
New energy vehicle charger
Rail power supply
Custom power supply
Module power supply
Switching power supply
Online Message
If you’re interested in us or our products, feel free to leave us a message.